3-1/2 Inch M/F Aluminum Sealing Fitting (V/H)
cULus Listed logo

Catalog Number
PMEYAM-350-A
Sealing Fittings by Perma-Cote
Description

PVC coated Sealing Fittings are used in conduit runs to stop gasses, vapors or flames from migrating from one part of the conduit system to another, thus limiting the spread of any potential explosion and enhancing safety. The PVC and urethane coatings of the fittings protects them from corrosive atmospheres so they can continue to function in hazardous locations. Precise coating of threads, quality control of protective coating thickness and P5SA™ plug installation verification on sealing fittings all allow for a level of assurance that proper plug engagement and installation will be performed correctly.

Additional Product Description

Available in several different configurations and with optional breathers and drains to accommodate installation in a variety of locations and positions.

Application
Stop gasses, vapors or flames from migrating from one part of the conduit system to another, thus limiting the spread of any potential explosion and enhancing safety
Features
40 mil gray PVC exterior coating
2 mil green urethane interior coating
10 trade sizes from 1/2" through 4"
Sealing sleeves on all conduit openings
P5SA Plug Verification to ensure proper plug engagement

General Information

Environment
Hazardous Location
Trade Size
3-1/2
Material
ALUMINUM
Material
ALUMINUM
Exterior Finish
A nominal .040 inch (40 mil) gray PVC coating
Interior Finish
A nominal .002 inch (2 mil) green urethane
Sealing Sleeves
All conduit openings
Sealing Orientation
Vertical or Horizontal
Hub Type
Male/Female
Dimensions
Dimension A (Inches)
9.19
Dimension B (Inches)
4.83
Turning Radius
3.44
Standards
CSA
C22.2 No. 30
NEC/CEC
Class II, Division 1, Groups F, G
NEC/CEC
Class II, Division 2, Groups F, G
NEC/CEC
Class III
NEC/CEC
Class I, Division 1 & 2, Groups C, D
UL 1203
E476062

Technical Information

Conduit Body
EYAM
Feed Type
VERTICAL/HORIZONTAL
Fitting Configuration
M/F
Fitting Type
SEALING FITTING
Product Category
HAZARDOUS LOCATION FITTING
Product Family
Sealing Fittings
Rating
Hazardous Location
Notes
These sealing fittings should be used with a suitable system of sealing compound, such as Chico A, Chico X or Chico A-P from Crouse-Hinds. Follow the installation instructions included with the sealing compound.